Schneider Electric MV Drives Specifications

Schneider Electric Altivar 1000 medium voltage drive:

Altivar 1000
Topology 3-level Neutral Point Clamped Voltage Source Inverter
Input section Diode 12-pulse or 24-pulse or HV IGBT based 3L-NPC AFE
Input voltage 2300V, 3300V
Efficiency 99% at rated load for drives with diode rectifier (without input transformer), no data for active front end rectifier
Input power quality 12-pulse IEEE 519 compliance – In/Isc ratio dependent, 24-pulse and AFE meets IEEE 519; PF>0.96 at rated load for diode rectifier, and PF>0.98 at rated load for AFE rectifier
DC link section common DC link capacitors
Output section HV IGBT based 3-level NPC voltage source inverter
Output power air-cooled 3300V drives: 1100-4500kW (1474-6032HP); water-cooled 3300V drives: 1300-11570kW (1742-15509HP)
Output voltage 0-2300V; 0-3300V
Output frequency 5-70Hz; extended 5-140Hz
Field weakening no data
Switching frequency no data
Output waveform 5-level line-to-line voltage waveform
Motor type induction or synchronous as option
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes
Cooling air-cooled and water-cooled
Control scheme V/f, flux vector control with and without encoder
Dynamic speed error no data
Steady-state speed error 0.5% without encoder and 0.05% with encoder
Torque response time 5ms
Torque accuracy no data
Modulation technique hysteresis modulation
Special features -

References:

  1. Concentrated savings for your applications. Altivar 1000. Medium-voltage variable speed drive

Leave a Reply