Ansaldo Sistemi Industriali MV Drives Specifications

Ansaldo Sistemi Industriali (ASI) medium voltage drives technical data:

Silcovert TN
Topology 3-level Neutral Point Clamped Voltage Source Inverter
Input section Diode 12-pulse or 24-pulse or HV IGBT based 3L-NPC AFE
Input voltage 3300V
Efficiency >98% at rated load for drives with diode rectifier, AFE – no data
Input power quality 12-pulse IEEE 519 compliance – In/Isc ratio dependent, 24-pulse and AFE meets IEEE 519; PF>0.96 at rated load for diode rectifier, >0.98 for active front end
DC link section common DC link capacitors
Output section HV IGBT based 3-level NPC VSI
Output power air cooled: 1170-4740kW (1568-6356HP); water cooled: 1390-12570kW (1864-16856HP)
Output voltage 0-3300V
Output frequency normal: 5-70Hz; extended: 5-140Hz
Field weakening no data
Switching frequency no data
Output waveform 5-level line-to-line voltage waveform
Motor type induction or synchronous
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes
Cooling air-cooled or water-cooled
Control scheme V/Hz, Sensorless Vector Control, FOC (with encoder)
Dynamic speed error no data
Steady-state speed error 0.01% with encoder
Torque response time 5ms
Torque accuracy no data
Modulation technique hysteresis modulation
Special features -
Silcovert GN
Topology 3-level Neutral Point Clamped Voltage Source Inverter
Input section Diode 12-pulse or 24-pulse or IGCT based 3L-NPC AFE
Input voltage 3300V
Efficiency >98% at rated load
Input power quality 12-pulse IEEE 519 compliance – In/Isc ratio dependent, 24-pulse and AFE meets IEEE 519; PF>0.98
DC link section common DC link capacitors
Output section IGCT based 3-level NPC VSI
Output power 7000-17800kW (9387-23870HP)
Output voltage 0-3000V for diode rectifier; 0-3300V for AFE
Output frequency normal: 10-65Hz; extended: 10-110Hz
Field weakening no data
Switching frequency no data
Output waveform 5-level line-to-line voltage waveform
Motor type induction or synchronous
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes
Cooling water-cooled
Control scheme FOC
Dynamic speed error no data
Steady-state speed error 0.01% with encoder
Torque response time 5ms
Torque accuracy no data
Modulation technique hysteresis modulation
Special features -
Silcovert S
Topology Load Commutated Inverter
Input section SCR 6-pulse, 12-pulse or 24-pulse
Input voltage 6000V
Efficiency >98,5% at rated load
Input power quality 6-pulse does not meet IEEE 519; 12-pulse IEEE 519 compliance – In/Isc ratio dependent, 24-pulse and AFE meets IEEE 519; PF – varying with the load – reactive power compensation is necessary
DC link section DC link reactor
Output section 6-pulse or 12-pulse SCR load commutated inverter
Output power 1-40MW (1341-53640HP)
Output voltage 0-6000V
Output frequency 0-120Hz
Field weakening no data
Switching frequency load commutation
Output waveform high output current harmonics resulting torque pulsations especially for 6-pulse inverters
Motor type synchronous
Overload no data
Cooling forced-air- or water-cooled
Control scheme no data
Dynamic speed error no data
Steady-state speed error 0.01% with encoder
Torque response time no data
Torque accuracy no data
Modulation technique load commutation
Special features high efficiency
Silcovert C
Topology Cycloconverter
Input section 3 antiparallel SCR 6-pulse converters or 3 antiparallel SCR 12- pulse converters
Input voltage 1200-1500V
Efficiency >95% at rated load
Input power quality PF – varying with the load
DC link section no DC link
Converter power 3650-10700kVA air-cooled; 3750-11400kVA water-cooled
Output voltage 0-1500V for 6-pulse; 0-3300V or 0-4160V for 12-pulse configuration
Output frequency 0-24Hz, up to 720 rpm for 2-pole motor and 60Hz main frequency
Field weakening no data
Switching frequency natural commutation
Output waveform no data
Motor type synchronous or induction
Overload no data
Cooling air- or water-cooled
Control scheme no data
Dynamic speed error no data
Steady-state speed error 0.01% with encoder
Torque response time no data
Torque accuracy no data
Modulation technique natural commutation
Special features low speed, high torque applications

References:

  1. Technical Brochure. SILCOVERT-TN, 3300V, 1300 to 14400kVA
  2. Technical Brochure. SILCOVERT-GN, 9000 to 36000kVA
  3. SILCOVERT S. MV LCI Drives for synchronous motors and generators up to 40MW
  4. SILCOVERT C. Direct AC/AC Cycloconverter
  5. Ansaldo Sistemi Industriali Power Electronics for Industrial Applications

Leave a Reply