Allen-Bradley (Rockwell Automation) MV Drives Specifications

Rockwell Automation manufactures three medium voltage drive types – all of them are CSI topology. The main differences between types are: power range, input section configuration, cabinets design – footprint, cooling and control voltage.

PowerFlex 7000A ‘A’ Frame
Topology Current Source Inverter
Input section PWM SGCT based rectifier with input capacitors, 6-pulse SCR rectifier, 6 SCRs/SGCTs for 2400V (2 per phase); 12 SCRs/SGCTs for 3300V and 4160V (4 per phase); 18 SCRs/SGCTs for 6600V (6 per phase); integral input contactor + line reactor (RPDTD, RPLR, R6LR), integral or remote isolation transformer (RPTX, RPTXI, R6TX, R6TXI), inherent regenerative braking capability
Input voltage 2400V, 3300V, 4160V, 6600V
Efficiency >98% 6-pulse rectifier at rated load, >97.5% PWM rectifier at rated load
Input power quality 6-pulse rectifier doesn’t meet IEEE 519 requirements – installation of passive LC input filters is necessary – current THD<6% with filters, PWM meets IEEE 519 – current THD<5%, PF>0.98 for 30-100% load
DC link section DC link reactor or DC link Common Mode Choke in Direct-to-Drive technology
Output section PWM SGCT based inverter with output capacitors, 6 SGCTs for 2400V (2 per phase); 12 SGCTs for 3300V and 4160V (4 per phase); 18 SGCTs for 6600V (6 per phase);
Output power 0.15-0.9MW (200-1200HP)
Output voltage 0-2300V, 0-3300V, 0-4160V, 0-6600V
Output freuency 0.2-75Hz
Field weakening no data
Switching frequency SGCTs<540Hz
Output waveform sinusoidal, output capacitors are used
Motor type induction or synchronous
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes for Heavy Duty drives (applications with constant torque)
Cooling forced air
Control scheme IFOC
Dynamic speed error no data
Steady-state speed error 0.1% without encoder, 0.01-0.02% with encoder
Torque response time no data
Torque accuracy no data
Modulation technique SHE (preffered) or SVM in rectifier, TPWM at low speed (0,5-37Hz) and SHE at high speed (>37Hz) in inverter
Special features Small footprint, integral input starter or integral input transformer
PowerFlex 7000 ‘B’ Frame
Topology Current Source Inverter
Input section PWM SGCT based rectifier with input capacitors, 6-pulse SCR rectifier, component count: 6 SCRs/SGCTs for 2400V (2 per phase); 12 SCRs/SGCTs for 3300V and 4160V (4 per phase); 18 SCRs/SGCTs for 6600V (6 per phase);
18-pulse SCR rectifier, component count: 6 SCRs for 2400V, 3300V, 4160V and 6600V;
line reactor (RPDTD, RPLR, R6LR), isolation transformer (RPTX, R6TX, R18TX), inherent regenerative braking capability
Input voltage 2400V, 3300V, 4160V, 6600V
Efficiency >98% 6-pulse and 18-pulse rectifier at rated load, >97.5% PWM rectifier at rated load
Input power quality 6-pulse rectifier doesn’t meet IEEE 519 requirements – installation of passive LC input filters is necessary – current THD<6% with filters, 18-pulse meets IEEE 519 – current THD <5.6%, PWM meets IEEE 519 – current THD<5%, PF>0.98 for 30-100% load
DC link section DC link reactor or DC link Common Mode Choke in Direct-to-Drive technology
Output section PWM SGCT based inverter with output capacitors, 6 SGCTs for 2400V (2 per phase); 12 SGCTs for 3300V and 4160V (4 per phase); 18 SGCTs for 6600V (6 per phase);
Output power 0.15-4.1MW (200-5500HP)
Output voltage 0-2300V, 0-3300V, 0-4160V, 0-6600V
Output freuency 0.2-85Hz
Field weakening no data
Switching frequency SGCTs<540Hz
Output waveform sinusoidal, output capacitors are used
Motor type induction or synchronous
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes for Heavy Duty drives (applications with constant torque)
Cooling forced air
Control scheme IFOC
Dynamic speed error no data
Steady-state speed error 0.1% without encoder, 0.01-0.02% with encoder
Torque response time no data
Torque accuracy no data
Modulation technique SHE (preffered) or SVM in rectifier, TPWM at low speed (0,5-37Hz) and SHE at high speed (>37Hz) in inverter
Special features -
PowerFlex 7000L ‘C’ Frame
Topology Current Source Inverter
Input section PWM SGCT based rectifier with input capacitors, component count: 12 SGCTs for 4160V (4 per phase); 18 SGCTs for 6600V (6 per phase);
18-pulse SCR rectifier, component count: 6 SCRs for 4160V and 6600V;
line reactor (RPDTD, RPLR), isolation transformer (R18TX), inherent regenerative braking capability
Input voltage 4160V, 6600V
Efficiency >98% 18-pulse rectifier at rated load, >97.5% PWM rectifier at rated load
Input power quality 18-pulse meets IEEE 519 – current THD <5.6%, PWM meets IEEE 519 – current THD<5%, PF>0.98 for 30-100% load
DC link section DC link reactor or DC link Common Mode Choke in Direct-to-Drive technology
Output section PWM SGCT based inverter with output capacitors, 12 SGCTs for 4160V (4 per phase); 18 SGCTs for 6600V (6 per phase);
Output power 2.2-6.3MW (3000-8500HP)
Output voltage 0-4160V, 0-6600V
Output freuency 0.2-85Hz
Field weakening no data
Switching frequency SGCTs<540Hz
Output waveform sinusoidal, output capacitors are used
Motor type induction or synchronous
Overload 110% rated current for 1 min. every 10 minutes or 150% rated current for 1 min. every 10 minutes for Heavy Duty drives (applications with constant torque)
Cooling liquid
Control scheme IFOC
Dynamic speed error no data
Steady-state speed error 0.1% without encoder, 0.01-0.02% with encoder
Torque response time no data
Torque accuracy no data
Modulation technique SHE (preffered) or SVM in rectifier, TPWM at low speed (0,5-37Hz) and SHE at high speed (>37Hz) in inverter
Special features -

Please let me know or write your comments if something should be corrected or clarified.